EIA calculation: boiler flue gas calculation
1 Kg coal produces 8.5 m3 flue gas (experience); 1 Kg coal in chain furnace produces 10.35 m3 flue gas;
Source strength calculation formula:
QSO2:\(Q=G×2×0.8×S×(1-ηS)\);
In the formula:
G-calcium consumption, mg/s;
S-sulphur content in coal;
ηS-desulfurization efficiency, %, grit water bath, water film is 40%, limestone-gypsum method is 90%.